      sales@gninstruments.com

      Location -> Products -> Flow -> Flowmeter For Gas

      Type:CX-VFM vortex flow meter

      Illustrate:CX-VFM vortex flow meter can be used for measuring gas,and it has price edge,and the temperature of gas can reach to -50-250C

      CX-VFM Vortex Flow Meter


      Working principle 
      To install a vortex generator(bluff body)in the fluid,which can produces regular vortex at both sides of the vortex generator altematively.Such vortex is called Karman Vortex.Vortex trains are asymmetrically arranged at the downstream of the vortex geberator. Suppose the generating frequency of the vortex is f,the average speed of the incoming flow of the tested medium is V,the head-on width of the vortex generator is d,and the diameter of the flowmeter is D,and base on the principles of Karman Vortex,the following relations will be obtained:  


          
      cart(1)
                         f=StV/d           Formula (1)      

      Note:f- Suppose the generating frequency of the vortex
           St-Strouhal number
           V-average flow velocity at both sides of the vortex generator
      d- the vortex geberator body width
       
      Thus, by measuring the Carmen frequency of vortex separation of instantaneous flow rate can be calculated. Among them, Strouhal number ( St ) is a dimensionless unknown, Figure ( two) said the Strouhal number ( St ) and Reynolds number ( Re ) relationship.


                                                                    chart(2)
      In the curve St = 0.17straight section, whirlpool release frequency and velocity proportional to, namely the vortex flow sensor measurement range. As long as the detected frequency f can be obtained within the tube by the flow rate of the fluid, flow velocity and volume flow rate V. The measured pulse number and volume ratio, called the instrument constant ( K ), see type (2)
                             K=N/Q(1/m³)             Formula (2) 
      K=Instrument constant(1/m³) 
      N=Pulse number
      Q=Volume flow(m³)

      Main technical index                                 Unit(1)


      Nominal diameter(mm) 25,40,50,65,80,100,125,150,200,
      250,300,(300~1000 Insert type)
      Nominal pressure (MPa) DN25-DN200 4.0(>4.0 Supply agreement),
      DN250-DN300 1.6(>1.6 Supply agreement)
      Medium temperature(℃) Piezoelectric type:-40~260,-40~320;Capacitance type
      : -40~300, -40~400,-40~450(Supply agreement)
      Body material 1Cr18Ni9Ti,(Other materials supply agreement)
      Allowable vibration acceleration Piezoelectric type:0.2g     Capacitance type:1.0~2.0g
      Accuracy ±1%R,±1.5%R,±1FS;Insert type:±2.5%R,±2.5%FS
      Range of 1:6~1:30
      Power supply voltage Sensor:+12V DC,+24V DC;Transmitter:
      +12V DC ,+24V DC;Battery type:3.6V Battery
      Output signal Square wave pulse ( not including the battery power supply type ):
       high level or low level5V,1V; current: 4~ 20mA
      Pressure loss coefficient In line with the JB / T9249standard Cd = 2.4
      Explosion proof marks Intrinsic safety type: Exd IA CT2-T5 flameproof type: Exd CT2-T5
      Protection grade The ordinary IP65  diving type IP68
      Environmental conditions Temperature - 20~ 55,5% ~ 90% of relative humidity,
       atmospheric pressure is 86 ~ 106kPa
      Applicable medium Gas, liquid, steam
      Transmission distance Three wire system pulse output type: < 300m, 
      two line standard current output type 
      (4 ~ 20mA ): load resistance less than 750ohm
       

      Table (2) reference conditions of vortex flow sensors flow rate range table

      Meter diameter
      (mm)
      Liquid Gas
      Measuring range
      (m3/h)
      Output 
      frequency range(Hz)
      Measuring range
      (m3/h)
      Output 
      frequency range(Hz)
      25 1.2~16 25~336
       
      8.8~55 190~1140
      40 2~40 10~200 27~205 140~1040
      50 3~60 8~160 35~380 94~1020
      80 6.5~130 4.1~82 86~1100 55~690
      100 15~220 4.7~69 133~1700 42~536
      150 30~450 2.8~43 347~4000 33~380
      200 45~800 2~31 560~8000 22~315
      250 65~1250 1.5~25 890~11000 18~221
      300 95~2000 1.2~24 1360~18000 16~213
      (300) 100~1500 5.5~87
       
      1560~15600 85~880
      (400) 180~3000 5.6~87 2750~27000 85~880
      (500) 300~4500 5.6~88 4300~43000 85~880
      (600) 450~6500 5.7~89 6100~61000 85~880
      (800) 750~10000 5.7~88 11000~110000 85~880
      (1000) 1200~1700 5.8~88 17000~170000 85~880
      >(1000) Agreement   Agreement  
      Note: (300) to (1000) diameter for insertion type

      Instrument installation dimensions: see figure ( five ), map ( six)

              


      Vortex flow meter selection table

      Spectrum Explain
      LU   Vortex flow meter
      G   Sensor
      Detection mode B   Piezoelectric sensor
      E   Capacitance type sensor
      Connection mode   1 Only the full pipe type Flange connection
      2 Only the full pipe type The flange clamp type
      3 Only to insert type Simple insertion type
      4 Only to insert type Insertion type ball valve
      Measurement of medium   2     Liquid
      3     Gas
      4     Steam
      Nominal diameter   02

      30
       
       

       
      DN25
      …              unit:mm
      DN300
      The use of the environment   P   Ordinary type
      B   Explosion proof type
      Output signal   1   Pulse output
      2   4 ~ 20mA output current, liquid crystal display
      3   RS-485 communication
      4   Battery powered, with temperature, pressure compensation
      5   The temperature and pressure compensation for one,
      4 ~ 20mA current output type
      6   The temperature and pressure compensation integrated, 
      battery power supply type
      Type description For example: LUGE2405-P2 full pipe type capacitive vortex flow meter, a flange clamp connection, medium for steam
      Instrument path for DN50, general 4~ 20mA output current signal

       Sensor the nominal size of the code table
      Nominal diameter  DN  mm 25 32 40 50 65 80 100 125 150 200 250
      Tag number 02 03 04 05 06 08 10 12 15 20 25
      Nominal diameter  DN mm 300 350 400 450 500 600 700 800 1000 1200 1500
      Tag number 30 35 40 45 50 60 70 80 A0 A2 A5
       

      Last:Thermal gas mass flow meter Next:CX-WGFM-XML wet gas flow meter

      Contact Us

      Office Address: Room 402, No. 650, Xinzhuan Rd., Jiuting Town, Songjiang District, Shanghai, China (Mainland)

      Phone:021-57635022

      E-mail:info@gnflowmeter.com

      E-mail:sales@gninstruments.com

      關(guān)閉