      Type:special thermocouple(thermal resistance)

      Illustrate:We design special structure for different occasion to directly measure the temperature of liquid, vapor, gas or solid surface ranging from -200C~1600C

      Special Thermocouple(Thermal Resistance)

       

      Application
       

      We design special structure for different occasion to directly measure the temperature of liquid, vapor, gas or solid surface ranging from -200C~1600C

      Operation theory
      Thermocouple electrode are made of two different materials. Temperature difference between measuring end and reference end results in pyroelectric potential, then display meter indicates the corresponding temperature to the pyroelectric potential.
      It is based on that material temperature change of its resistance. When resistance value changes, the working instrument will display relevant temperature.

      Main technical parameters
      Executive standard
      IEC584
      IEC751
      JB/T5582-1991

      Nominal pressure
      It generally refers to sustainable static pressure on protection tube from outside without breakage. It concerns not only material, diameter, wall thickness of protection tube, but structure and mounting way of the tube, flow speed and category of tested media as well.
      Insulation resistance at normal temperature
      The insulation resistance between electrode and protection tube of the thermocouple shall be no less than 1000MW. m under condition that environment temperature is 20±15C, relative humidity is no more than 80%, and test voltage is D.C.500±50V.
      The insulation resistance between electrode and protection tube of thermal resistance shall be less than 100MΩ under condition that environment temperature is 15±35C, relative humidity is no more than 80%, and testing voltage is D.C.10~100V.

      Thermocouple

       
      Type
       
      Graduation
      Tolerance class
      Tolerance value Measuring range ℃ Tolerance value Measuring range ℃
      WRN K ± 1.5C -40~+375 ± 2.5C -40~+333
      ± 0.004|T| 375~-1000 ± 0.0075|T| 333~1200
      WRE E ± 1.5C -40~+375 ± 2.5C -40~+333
      ± 0.004|T| 375~800 ± 0.0075|T| 333~900
      WRP S ± 1C 0~+1100 ± 2.5C 0~600
      ± [1+0.003(t-1100)] 1100~1600 ± 0.004|T| 600~1600
      WRQ R ± 1C 0~+1100 ± 2.5C 0~+1100
      ± [1+0.003(t-1100)] 1100-1600 ± 0.0025|T| 1100~1600
      WRR B --- --- --- ---
      --- --- ± 0.00425T| 600~1700
       Thermal resistance
      Type Graduation Temperature range Accuracy class Tolerance
      WZP Pt100 -200~+500 A ±(0.15+0.002)|t|
      B ±(0.30+0.005)|t|
      WZC Cu50  Cu100 -50~+100 -- ±(0.30+0.005)|t|

      Last:Without the Next:thermocouple resistance with so..

      Contact Us

      Office Address: Room 402, No. 650, Xinzhuan Rd., Jiuting Town, Songjiang District, Shanghai, China (Mainland)

      Phone:021-57635022

      E-mail:info@gnflowmeter.com

      E-mail:sales@gninstruments.com

      關(guān)閉
    • <blockquote id="o6sq2"><tfoot id="o6sq2"></tfoot></blockquote>
      <center id="o6sq2"></center>
    • <th id="o6sq2"><nav id="o6sq2"></nav></th>
    • <ul id="o6sq2"><tbody id="o6sq2"></tbody></ul>
        <samp id="o6sq2"></samp><ul id="o6sq2"><tbody id="o6sq2"></tbody></ul>